Thermal Current Rating
|
-
|
300A
|
Intermittent Current Rating:
|
30% Duty
|
-
|
550A
|
40% Duty
|
-
|
475A
|
50% Duty
|
-
|
425A
|
60% Duty
|
-
|
385A
|
70% Duty
|
-
|
360A
|
Rated Fault Current Breaking Capacity (Icn) 5ms Time Constant:
|
Blowouts
|
1000A at 96V D.C.
|
No Blowouts
|
1000A at 48V D.C.
|
Rated Fault Current Breaking Capacity (Icn) Resistive Load:
|
Blowouts
|
-
|
No Blowouts
|
-
|
Maximum Recommended Contact Voltages
|
Blowouts
|
-
|
96V
|
No Blowouts
|
-
|
48V
|
Typical Voltage Drop per pole across New Contacts at 300A
|
30mV
|
|
Mechanical Durability
|
> 10,000 Cycles
|
Coil Voltage Available (Us) (Rectifier board required for A.C.)
|
0 - 0V
|